Pin 12 (CREF) controls the sense of all the digital inputs (X13 pins 1 to 9) and should be permanently
wired, dependent on the user requirements, as described below:
Active high
: c24VDC to pin1 and 0V to pin 12.
The digital inputs will be active when a voltage of +24VDC (±20%) is applied to them and will sink a
maximum of 20mA.
Active low
: c24VDC to pin12 and 0V to pin 1.
The digital inputs will be active when grounded and will source a maximum of 20mA.
The +24VDC supply mentioned above is from an externally generated 24VDC supply which should
have a current capability of at least 3A to fulfill all the current requirements of the above loads.
The sense of the inputs can also be controlled individually in Mint using the keyword
INPUTACTIVELEVEL
. See also section 2.6 on page 26.
3.3.1.1
Thermal switch connection
It is recommended to wire the motor’s thermal switch, via a relay, to an input on connector X13.
Using suitable code, this provides a way for the Mint program to respond to motor overtemperature
conditions. A typical circuit, using DIN11 as the input, is shown below.
A
B
Motor
thermal switch
connections
CREF
X13
1
12
DIN10 (
IN.10
)
2
DIN11 (
IN.11
)
3
DIN12 (
IN.12
)
4
DIN13 (
IN.13
)
5
DIN14 (
IN.14
)
6
DIN15 (
IN.15
)
7
DIN16 (
IN.16
)
8
DIN17 (
IN.17
)
9
Relay
External
24VDC
supply
+24VDC
0V
Figure 16 - Motor thermal switch circuit
Summary of Contents for MintDrive
Page 2: ...MN1274 06 2001 Installation Manual Installation Manual...
Page 3: ......
Page 13: ...xii...
Page 56: ...43 Figure 22 Auxiliary encoder circuit...
Page 91: ...78...
Page 97: ...84...
Page 109: ...96...
Page 111: ...98 Figure A 1 MintDrive Closed Loop System Motor Speed Filter 16 Sample Filter...
Page 119: ...106...
Page 141: ...128...
Page 147: ...134...
Page 154: ......