14
2.3.4
Wire sizes
Input and output wire size is based on the use of copper conductor wire rated at 167°F (75°C).
The following tables describe the wire size to be used for power connections and the ratings of the
protection devices.
Catalog Number
Incoming Power
g
D Type
Input
Wire Gauge
Nominal
Continuous
D-Type
Input
Input
Fuse
Wire Gauge
Nominal
Input
Voltage
Continuous
Output
Amps
(RMS)
Input
Breaker
(A)
Time
Delay
(A)
AWG
mm
2
MD1A02
xx-xxxx
115V (1
φ
)
2.5A
6
6
14
2.5
MD2A02
xx-xxxx
230V (1
φ
)
2.5A
6
6
14
2.5
MD1A05
xx-xxxx
115V (1
φ
)
5A
10
10
14
2.5
MD2A05
xx-xxxx
230V (1
φ
)
5A
10
10
14
2.5
MD1A07
xx-xxxx
115V (1
φ
)
7.5A
16
16
14
2.5
MD2A07
xx-xxxx
230V (1
φ
)
7.5A
16
16
14
2.5
MD1A10
xx-xxxx
115V (1
φ
)
10A
20
20
14
2.5
MD2A10
xx-xxxx
230V (3
φ
)
10A
20
20
14
2.5
MD1A15
xx-xxxx
115V (1
φ
)
15A
32
32
12
2.5
MD2A15
xx-xxxx
230V (3
φ
)
15A
32
32
12
2.5
Note:
All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may
be used per NEC and local codes. Recommended fuses/breakers are based on 77°F (25°C)
ambient, maximum continuous control output current and no harmonic current.
Summary of Contents for MintDrive
Page 2: ...MN1274 06 2001 Installation Manual Installation Manual...
Page 3: ......
Page 13: ...xii...
Page 56: ...43 Figure 22 Auxiliary encoder circuit...
Page 91: ...78...
Page 97: ...84...
Page 109: ...96...
Page 111: ...98 Figure A 1 MintDrive Closed Loop System Motor Speed Filter 16 Sample Filter...
Page 119: ...106...
Page 141: ...128...
Page 147: ...134...
Page 154: ......