93
Code
Check
Problem
17
Over speed fault
Motor RPM exceeded 110% of programmed MAX Motor speed.
Type
PRINT MAXMOTORSPEED
. If the value returned exceeds
the maximum mechanical speed of the motor specified in the
catalog, type
MAXMOTORSPEED =
xxxx
where xxxx is the
maximum speed listed in the catalog, in RPM.
You should retune the motor after changing this parameter.
Check the Mint demanded velocity by using either the QuickWatch
tab or Capture tab and compare with the
MAXMOTORSPEED
parameter. If the Mint demanded velocity is greater than the
maximum speed of the motor, modify your Mint program to
generate a slower demand velocity.
19
Control temp fault
Temperature of drive heatsink exceeded safe level.
Check correct operation of fans (if fitted) and ensure that they are
clear of dirt.
Check the ambient temperature around the drive.
Ensure that the unit is adequately ventilated.
If the problem persists add additional cooling.
21
Lost User Data
Battery backed RAM parameters have been lost or corrupted.
If the fault did not clear automatically after power-up, enter the
“Drive Setup” dialog and retune the MintDrive by following the
tuning setup (see section 4.2 on page 51).
22
Microprocessor
reset
Turn off the power supply and wait for the residual Bus voltage to
reach 0VDC before turning on.
Power-cycle the MintDrive. Check power-supply
26
New Base Id fault
Control board was changed since last operation.
Power-cycle the MintDrive.
31
Feedback module
fault
Indicates a problem with the feedback device.
If the problem persists after you have power-cycled the MintDrive
and you are using an encoder, rotate the motor shaft and
power-cycle the MintDrive again
32
Serial watchdog fault Inter-processor communication problem.
Abort any program that may be running by pressing CTRL+E.
Type
CANCEL
. If the fault re-appears, power-cycle the MintDrive.
Summary of Contents for MintDrive
Page 2: ...MN1274 06 2001 Installation Manual Installation Manual...
Page 3: ......
Page 13: ...xii...
Page 56: ...43 Figure 22 Auxiliary encoder circuit...
Page 91: ...78...
Page 97: ...84...
Page 109: ...96...
Page 111: ...98 Figure A 1 MintDrive Closed Loop System Motor Speed Filter 16 Sample Filter...
Page 119: ...106...
Page 141: ...128...
Page 147: ...134...
Page 154: ......