131
EMC filters
The EMI or mains filter should be mounted next to the power supply. For the connection to and from
the mains filter screened cables should be used. The cable screens should be connected to screen
clamps on both sides. An exception to this is the analog command signal.
Grounding (Earth)
For safety reasons (VDE0160), all Baldor components must be connected to ground with a separate
wire. Ground connections must be made from the central ground to the regen resistor enclosure and
from the central ground to the Shared Power Supply.
C.1.5
EMC installation suggestions
To ensure electromagnetic compatibility (EMC), the following installation points should be considered to
help reduce interference:
H
Grounding of all system elements to a central ground point
H
Shielding of all cables and signal wires
H
Filtering of power lines.
A proper enclosure should have the following characteristics:
H
All metal conducting parts of the enclosure must be electrically connected to the back plane.
These connections should be made with a grounding strap from each element to a central
grounding point.
*
H
Keep the power wiring (motor and power cable) and control wiring separated. If these wires must
cross, be sure they cross at 90 degrees to minimize noise due to induction.
H
The shield connections of the signal and power cables should be connected to the screen rails or
clamps. The screen rails or clamps should be conductive clamps fastened to the cabinet.
**
H
The cable to the regeneration resistor must be shielded. The shield must be connected to ground at
both ends.
H
The location of the AC mains filter has to be situated close to the drive so the AC power wires are as
short as possible.
H
Wires inside the enclosure should be placed as close as possible to conducting metal, cabinet walls
and plates. It is advised to terminate unused wires to chassis ground.
*
H
To reduce ground current, use the largest suitable wire available for ground connections.
*
Grounding in general describes all metal parts which can be connected to a protective conductor,
e.g. housing of cabinet, motor housing, etc. to a central ground point. This central ground point is
then connected to the main plant (or building) ground.
**
Or run as twisted pair at minimum.
Summary of Contents for MintDrive
Page 2: ...MN1274 06 2001 Installation Manual Installation Manual...
Page 3: ......
Page 13: ...xii...
Page 56: ...43 Figure 22 Auxiliary encoder circuit...
Page 91: ...78...
Page 97: ...84...
Page 109: ...96...
Page 111: ...98 Figure A 1 MintDrive Closed Loop System Motor Speed Filter 16 Sample Filter...
Page 119: ...106...
Page 141: ...128...
Page 147: ...134...
Page 154: ......