34 Start-up
04
T16 scale
Defines the reference multiplier/actual
value divisor for the adapter module. The
parameter is effective only when the
Transparent 16 profile is selected AND the
drive is using the native communication
profile (eg, DCU or FBA) and a 16-bit
transparent Reference 1/Actual value 1.
With an ACS355 drive, the speed reference
from the PLC is multiplied by the value of
this parameter plus one. For example, if the
parameter has a value of 99 and a
reference of 1000 given by the master, the
reference will be multiplied by 99 + 1 = 100
and forwarded to the drive as 100000.
According to the DCU profile, this value is
interpreted as a reference of 100 rpm in the
drive.
With ACSM1, ACS850, ACQ810 and
ACS880, setting this parameter to 65535
provides the approximation of 1 = 1 rpm.
99
0…65535
Reference multiplier/actual value divisor
05
X1 MDI/MDIX
Defines the cable type connected to the
port.
The auto MDI/MDIX detection feature is
enabled by default. For each port, you can
disable auto MDI/MDIX and designate the
port as MDI port or designate the port as
MDIX port.
Connect MDI port to MDIX port via straight-
through twisted pair cabling. Both MDI-to-
MDI and MDIX-to-MDIX connections use
crossover twisted pair cabling.
0
= Auto
0
= Auto
Auto detect.
1
= MDI
Designates the port as MDI port.
2
= MDIX
Designates the port as MDIX port.
No.
Name/Value
Description
Default
Summary of Contents for FEPL-02 Ethernet POWERLINK
Page 4: ......
Page 10: ...10 Table of contents ...
Page 20: ...20 About the manual ...
Page 28: ...28 Mechanical installation ...
Page 63: ...Start up 63 2 To add the adapter module right click the IF3 list entry and then click Insert ...
Page 69: ...Start up 69 3 In the Project transfer dialog box click OK 4 Wait for the transfer to finish ...
Page 70: ...70 Start up When the transfer is finished the PLC starts up in the RUN mode ...
Page 90: ...90 Communication profiles ...
Page 100: ...100 Communication protocol ...
Page 104: ...104 Diagnostics ...
Page 108: ...108 Technical data ...