48 Start-up
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for ACSM1
drives
Description
50.01 FBA ENABLE
ENABLE
Enables communication between
the drive and the fieldbus adapter
module.
50.02 COMM LOSS
FUNC
Fault
2)
Enables fieldbus communication
fault monitoring.
50.03 COMM LOSS T
OUT
1.0 s
2)
Defines the fieldbus
communication break supervision
time.
50.04 FBA REF1
MODESEL
Position
Selects the fieldbus reference 1
scaling.
51.01 FBA TYPE
136
= ETH Pwrlink
1)
Displays the type of the fieldbus
adapter module.
51.02 FBA PAR2
(PROFILE)
0
(= CiA 402)
Selects the CANopen device
profile CiA 402.
51.03 FBA PAR3
(NODE ID)
3
2)
Defines the address of the
device.
51.27 FBA PAR
REFRESH
REFRESH
Validates the FEPL configuration
parameter settings.
10.01 EXT1 START
FUNC
FBA
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
34.03 EXT1 CTRL
MODE1
Position
Selects the position control mode
for external control location
EXT1.
62.24 POS START
MODE
PULSE
Positioning starts at the rising
edge of the pulse.
65.01 POS
REFSOURCE
Ref table
Reference and other positioning
parameters are read from
reference set 1/2.
65.04 POS REF 1 SEL
FBA REF1
Fieldbus reference 1 is the
source for the position reference
when reference set 1 is used.
1) Read-only or automatically detected/set
2) Example
Summary of Contents for FEPL-02 Ethernet POWERLINK
Page 4: ......
Page 10: ...10 Table of contents ...
Page 20: ...20 About the manual ...
Page 28: ...28 Mechanical installation ...
Page 63: ...Start up 63 2 To add the adapter module right click the IF3 list entry and then click Insert ...
Page 69: ...Start up 69 3 In the Project transfer dialog box click OK 4 Wait for the transfer to finish ...
Page 70: ...70 Start up When the transfer is finished the PLC starts up in the RUN mode ...
Page 90: ...90 Communication profiles ...
Page 100: ...100 Communication protocol ...
Page 104: ...104 Diagnostics ...
Page 108: ...108 Technical data ...