54 Start-up
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 47Eh (1150 decimal)
→
READY TO SWITCH ON.
•
Enter 47Fh (1151 decimal)
→
OPERATING (Speed mode).
51.02 FBA par2
(PROFILE)
0
(= CiA 402)
Selects the CANopen device
profile CiA 402.
51.03 FBA par3
(NODE ID)
3
2)
Defines the address of the
device.
51.27 FBA par refresh
Refresh
Validates the FEPL configuration
parameter settings.
10.01 Ext1 start func
FB
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
12.03 Ext1 ctrl mode
Speed
Selects the speed control mode
for external control location
EXT1.
21.01 Speed ref1 sel
FBA ref1
(Parameter
02.26
)
Selects fieldbus reference 1 as
the source for speed reference 1.
1) Read-only or automatically detected/set
2) Example
Drive parameter
Setting for ACS850
drives
Description
Summary of Contents for FEPL-02 Ethernet POWERLINK
Page 4: ......
Page 10: ...10 Table of contents ...
Page 20: ...20 About the manual ...
Page 28: ...28 Mechanical installation ...
Page 63: ...Start up 63 2 To add the adapter module right click the IF3 list entry and then click Insert ...
Page 69: ...Start up 69 3 In the Project transfer dialog box click OK 4 Wait for the transfer to finish ...
Page 70: ...70 Start up When the transfer is finished the PLC starts up in the RUN mode ...
Page 90: ...90 Communication profiles ...
Page 100: ...100 Communication protocol ...
Page 104: ...104 Diagnostics ...
Page 108: ...108 Technical data ...