Start-up 41
Parameter setting examples – ACS355
Speed control using the CiA 402 velocity mode (vl)
This example shows how to configure a speed control application
that uses the velocity mode (vl) of the CiA 402 profile.
When configuring the master, you need to map the following
objects to the transmit and receive PDOs. For an example, see
section
Mapping objects required for controlling the drive
page
.
The table below gives the recommended drive parameter settings.
CANopen
object
Output data
CANopen
object
Input data
0x6040
Control word
0x6041
Status word
0x6042
Target velocity
0x6044
Vl control effort
Drive parameter
Setting for ACS355
drives
Description
9802 COMM PROT SEL
4
= EXT FBA
Enables communication between
the drive and the fieldbus adapter
module.
5101 FBA TYPE
136
= ETH Pwrlink
1)
Displays the type of the fieldbus
adapter module.
5102 FB PAR 2
(PROFILE)
0
(= CiA 402)
Selects the CANopen device
profile CiA 402.
5103 FB PAR 3
(NODE ID)
3
2)
Defines the address of the
device.
3018 COMM FAULT
FUNC
1
= FAULT
2)
Enables fieldbus communication
fault monitoring.
3019 COMM FAULT
TIME
3.0 s
2)
Defines the fieldbus
communication break supervision
time.
5127 FBA PAR
REFRESH
1
= REFRESH
Validates the FEPL configuration
parameter settings.
Summary of Contents for FEPL-02 Ethernet POWERLINK
Page 4: ......
Page 10: ...10 Table of contents ...
Page 20: ...20 About the manual ...
Page 28: ...28 Mechanical installation ...
Page 63: ...Start up 63 2 To add the adapter module right click the IF3 list entry and then click Insert ...
Page 69: ...Start up 69 3 In the Project transfer dialog box click OK 4 Wait for the transfer to finish ...
Page 70: ...70 Start up When the transfer is finished the PLC starts up in the RUN mode ...
Page 90: ...90 Communication profiles ...
Page 100: ...100 Communication protocol ...
Page 104: ...104 Diagnostics ...
Page 108: ...108 Technical data ...