![background image](http://html.mh-extra.com/html/abb/fepl-02-ethernet-powerlink/fepl-02-ethernet-powerlink_user-manual_191086.webp)
86 Communication profiles
7
ALARM
1
Warning/Alarm
0
No warning/alarm
8
AT_
SETPOINT
1
OPERATION.
Actual value equals reference
(= is within tolerance limits, ie, in speed
control, speed error is 10% max. of nominal
motor speed).
0
Actual value differs from reference (= is
outside tolerance limits).
9
REMOTE
1
Drive control location: REMOTE (EXT1 or
EXT2)
0
Drive control location: LOCAL
10
ABOVE_
LIMIT
1
Actual frequency or speed equals or exceeds
supervision limit (set by drive parameter).
Valid in both directions of rotation.
0
Actual frequency or speed within supervision
limit
11
EXT_CTRL_
LOC
1
External Control Location EXT2 selected.
Note concerning ACS880:
This bit is
effective only if the fieldbus interface is set as
the target for this signal by drive parameters.
User bit 0 selection (06.33).
0
External Control Location EXT1 selected
12
EXT_RUN_
ENABLE
1
External Run Enable signal received.
Note concerning ACS880:
This bit is
effective only if the fieldbus interface is set as
the target for this signal by drive parameters.
User bit 1 selection (06.34).
0
No External Run Enable signal received
13…
14
Drive-specific (For information, see the drive documentation.)
15
FBA_ERROR
1
Communication error detected by fieldbus
adapter module
0
Fieldbus adapter communication OK
Bit
Name
Value
STATE/Description
Summary of Contents for FEPL-02 Ethernet POWERLINK
Page 4: ......
Page 10: ...10 Table of contents ...
Page 20: ...20 About the manual ...
Page 28: ...28 Mechanical installation ...
Page 63: ...Start up 63 2 To add the adapter module right click the IF3 list entry and then click Insert ...
Page 69: ...Start up 69 3 In the Project transfer dialog box click OK 4 Wait for the transfer to finish ...
Page 70: ...70 Start up When the transfer is finished the PLC starts up in the RUN mode ...
Page 90: ...90 Communication profiles ...
Page 100: ...100 Communication protocol ...
Page 104: ...104 Diagnostics ...
Page 108: ...108 Technical data ...