Communication objects
Communication objects
Product manual 2CKA001473B9679
│351
12.1.49 RTC - Request manual fan speed level
Name
Object function
Data type
RTC: Request manual fan speed
level
(Master)
Input
1.001 Switching
RTC: Request manual fan speed
level
(Slave)
Output
1.001 Switching
The communication object is used to transmit the request of the manual or automatic fan speed
level control of a slave device to the master device. This means that value 0 "Automatic fan
speed level control", the value 1 "Manual fan speed level control"
Notice
When the master/slave operation is activated, the object "RTC: Request manual
fan speed level (master)" of the master device for synchronisation must be
connected with object "RTC: Request manual fan speed level (slave)" of the
slave device.
12.1.50 RTC - Request fan speed level
Name
Object function
Data type
RTC: Request fan speed level
(Master)
Input
5.001 Percentage value
6.010 Counter value
RTC: Request fan speed level
(Slave)
Output
5.001 Percentage value
6.010 Counter value
The communication object is used to transmit the request of a fan speed level via the button
operation of a slave device to the master device. The values can be transmitted as percentage
values or counter values.
Notice
When the master/slave operation is activated, the object "RTC: Request fan
speed level (master)" of the master device for synchronisation must be
connected with object "RTC: Request fan speed level (slave)" of the slave
device.
12.1.51 RTC - Confirm fan speed level
Name
Object function
Data type
RTC: Confirm fan speed level
(Master)
Output
5.001 Percentage value
6.010 Counter value
RTC: Confirm fan speed level
(Slave)
Input
5.001 Percentage value
6.010 Counter value
The communication object is used to transmit the fan speed level confirmation of the master
device to a slave device. The values can be transmitted as percentage values or counter
values.