Description of application and parameters
Application "CO2 sensor"
Product manual 2CKA001473B9679
│158
11.5.14 CO2 controller — Send control value cyclic
Options:
Inactive
Every minute
Every 2 minutes
Every 3 minutes
Every 4 minutes
Every 5 minutes
Every 10 minutes
Every 15 minutes
Every 20 minutes
Every 45 minutes
Every hour
Every 2 hours
Every 3 hours
Every 4 hours
Every 5 hours
Every 6 hours
Every 12 hours
Once a day
If you wish to send the control value cyclically through the corresponding KNX communication
object, the corresponding time must be selected.
11.5.15 CO2 controller — Hysteresis (symmetrical)
Options:
50 ppm
100 ppm
150 ppm
200 ppm
250 ppm
300 ppm
The basic set value has a hysteresis. If the parameterised hysteresis value is
exceeded/undershot, the corresponding value is sent.
Notice
The parameter is available only when parameter "CO2 controller type" is set on
"Single stage", "Two-stage", "Three-stage" or "PI".