Description of application and parameters
Product manual 2CKA001473B9679
│63
11
Description of application and parameters
11.1
Application "Device settings"
11.1.1 Device enable - Application
Options:
Inactive
Enable application
■
Inactive:
– Application is not active.
■
Enable application:
– Application is active.
If the application is activated the device can be blocked temporarily via the 1- bit communication
object "EF: enable". No telegrams are sent on the bus via the communication object of the
device during a blockage. It can be enabled via an On or an Off telegram.
The following communication objects are available:
■
"EF: enable"
■
"EF: automatic switchover time"
The communication objects are enabled via the associated parameters.
Note
The following parameters can only be adjusted when the function "Device
enable" is set on "Enable application".
The parameters for application "Device enable" can be called up via
general
parameters
.
11.1.1.1
Enable with
Options:
On telegram
Off telegram
■
ON telegram:
– Devices are enabled via an On telegram.
■
Off telegram:
– Devices are enabled via an Off telegram.
The device is normally enabled with the receipt of an ON telegram via 1-bit communication
object "EF: enabled" and blocked with an OFF telegram. The parameter can invert this
behaviour.
11.1.1.2
After bus voltage recovery the device is