Description of application and parameters
Application "RTC"
Product manual 2CKA001473B9679
│96
11.4.13 Basic stage heating
Notice
Only available when the "Extended settings" parameter under "Heating control"
is set on "Yes".
11.4.14 Basic stage heating — Status object heating
Options:
No
Yes
■
No
– The parameter enables the "Status heating" communication object.
■
Yes
– The parameter enables the "Status heating" communication object.
An On telegram is sent on the bus via the 1-bit communication object as soon as the RTC is in
active heating mode.
If the controller is in cooling mode or in the inactive zone between heating and cooling, the RTC
sends an OFF telegram via the "RTC: Heating status" object.
11.4.15 Basic stage heating - Mode of the control value
Options:
Normal
Inverse
■
Normal:
– The mode of the control value can be used to adapt the control value to de-energised
opened (normal) valves.
– Normal: Means "Valve closed" de-energised closed.
■
Inverse
– The mode of the control value can be used to adapt the control value to de-energised
closed (inverse) valves.
– Inverse: Means "Valve open" de-energised opened.
The mode of the control valuecan be used to adapt electro-thermal drives.