Description of application and parameters
Application "CO2 sensor"
Product manual 2CKA001473B9679
│174
11.5.47 PI controller — Control value at measurement failure
Options
End priority
OFF with priority
ON with priority
If the internal or external measurement malfunctions or fails, a defined switch command can be
sent through this parameter.
Notice
The parameter is available only when parameter "CO2 controller type" is set on
"PI".
11.5.48 PI controller - Blocking object
Options:
Inactive
Active
The complete function of the CO2 sensor can be blocked using this parameter and with a 1 via
the corresponding communication object. Deactivation takes place by setting a value of 0.
Notice
The parameter is available only when parameter "CO2 controller type" is set on
"PI".
11.5.49 Behaviour at removing the blockage
Options:
Do not send any message
Send current value
If the sensor is enabled again after the receipt of an OFF telegram, the following parameters
can be selected:
■
Do not send:
– The sensor only sends its value when it has changed.
■
Send current value:
– The sensor sends its current value also when it has not changed.
Notice
The parameter is available only when parameter "Blocking object" is set on
"Active".