Description of application and parameters
Application "RTC"
Product manual 2CKA001473B9679
│94
11.4.9 Heating control - Heating type
Options:
PI continuous, 0 – 100% and PI PWM, On/Off:
■
Area (e.g. floor heating) 4°C 200 min
■
Convector (e.g. heater) 1.5°C 100 min
■
Free configuration
Fan coil:
■
Fan coil 4°C 90 min
■
Free configuration
Multiple heating types (panel heating, convector heating or fan coil) with preset parameters are
available to the user.
– If the required heating type is not available, individual parameters can be specified via the
free configuration.
Notice
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%,"PI PWM, On/Off“ or "Fan coil".
11.4.10 Heating control - P-component (x 0.1°C)
Options:
Setting option from 10 to 100
The P-component refers to the proportional range of a control. It fluctuates around the setpoint
value and can be used to influence control speed of a PI controller. The smaller the setpoint, the
faster the controller responds. However, to avoid the risk of an overshoot, this value should not
be set too low. A P-component from 0.1 to 25.5 K can be set.
Notice
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%,"PI PWM, On/Off“ or "Fan coil". In addition,
the "Heating type" parameter must be set on "Free configuration".