Description of application and parameters
Application "Function block x"
Product manual 2CKA001473B9679
│282
11.7.20.7
Colour for Zone 2 (starting at 1%)
Options:
Off
Yellow
Red-orange
Red
Violet
Blue
Green
White
■
Off:
– The LED is switched off.
■
Yellow - white:
– The LED lights up in the fixed colour at value telegrams for zone 2.
The parameter is used to specify the colour the LED lights up in when a telegram with a value is
received via the 1-byte communication object "Lx: status LED", which meets the following
conditions:
■
Value is ≥ 1% and
■
Value is < S1.
The default setting is "yellow".
The threshold value S1 is set via the parameter "Threshold between Zone 2 and 3" (%).
Note
The parameter can only be set if the "Operating mode" parameter and is set on
"Status illumination" and the "Object type for status object" parameter is set on
"1 byte 0-100%".
11.7.20.8
Threshold between Zone 2 and 3 (%)
Options:
Setting option from 1 to 98
The parameter is used to set the threshold value (S1) between Zone 2 and 3.
If the value received is < S1 and ≥ 1%, the LED lights up in the colour for zone 2.
If the value received is ≥ S1 and < S2, the LED lights up in the colour for zone 3.
Note
The parameter can only be set if the "Operating mode" parameter and is set on
"Status illumination" and the "Object type for status object" parameter is set on
"1 byte 0-100%".