Description of application and parameters
Application "Function block x"
Product manual 2CKA001473B9679
│272
11.7.17.3
Enable object
Options:
Deactivated
Activated
■
Deactivated:
– Communication object "Sx: enable" is not enabled. Local switchover of operating modes
via the device button is always possible and cannot be blocked temporarily.
■
Activated:
– Communication object "Sx: enable" is enabled. Local switchover of operating modes via
the device button can be blocked temporarily.
– If an On telegram (value "1") is received via the enabled object, local switchover of
operating modes is possible.
– If an Off telegram (value "0") is received via the enabled object, local switchover of
operating modes is blocked. This means that no telegram is sent via output object "Sx:
operating mode ...".
Note
If the "Enable object" parameter is activated, the following parameters can be
set:
■
"Object value enable object"
■
"Enable object after return of voltage"
11.7.17.4
Object value enable object
Options:
Normal
Inverse
■
Normal:
– If an On telegram (value "1") is received via communication object "Sx: enable", local
switchover of operating modes is possible. An Off telegram (value "0") deactivates the
function and no telegrams are sent on object "Sx: operating mode...".
■
Inverse:
– If an Off telegram (value "0") is received via communication object "Sx: enable", local
switchover of operating modes is possible. An On telegram (value "1") deactivates the
function and no telegrams are sent on object "Sx: operating modes ..."
The parameter is used to specify whether application "Set 1-button operating mode "RTC"" is
blocked temporarily at the receipt of an On or Off telegram.
Note
This parameter can only be set if the "Enable object" parameter is set on
"activated".