Description of application and parameters
Application "CO2 sensor"
Product manual 2CKA001473B9679
│155
11.5.9 CO2 controller — CO2 controller type
Options:
Inactive
Single-stage
Two-stage
Three-stage
PI
The control type for actuating the external fan is defined using this parameter.
11.5.10 CO2 controller — Permit change of the basic set value via bus
Options:
No
Yes
The basic set value defined for the first threshold can be optimised via the KNX bus, e.g.,
through a visualisation.
11.5.11 CO2 controller — Control value output format
Options:
Switch command
Priority
Percent
Byte
Scene
The output value when the respective threshold is exceeded or undershot is defined using this
parameter.
Notice
The parameter is available only when parameter "CO2 controller type" is set on
"Single stage", "Two-stage" or "Three-stage".
Notice
For selection of parameter setting "PI" only the selection between "Percent" or
"Byte" is available.