Description of application and parameters
Application "Device settings"
Product manual 2CKA001473B9679
│76
11.1.4.6
CO
2
value via
Options:
Internal measurement
Communication object
■
Internal measurement
– CO
2
value is measured on the device.
■
Communication object
– CO
2
value is fed via the bus.
The parameter can be used to select whether the CO
2
value is measured directly on the device
or fed to the device via a communication object via the bus.
Notice
– The parameter is only adjustable if the "Display CO
2
value" parameter is set
on "Yes".
– With devices without CO
2
module it is specified that the CO
2
value is sent
automatically to the device via a communication object.
– The above selection is cancelled.
11.1.4.7
Communication object data type
Options:
2 byte value (DPT 9.007)
1 byte value (DPT 5.001)
■
2-byte value (DPT 9.007)
– For EIS 5 (9.007), when the display of the value for relative humidity takes place via the
communication object.
■
1-byte value (DPT 5.001)
– For DPT scaling (5.001), when the display of the value for relative humidity takes place
via the communication object.
Notice
The parameter can only be set when parameter "Display relative humidity" is set
on "Yes". In addition, parameter "Relative humidity value above" must be set on
"Communication object".