Description of application and parameters
Application "Function block x"
Product manual 2CKA001473B9679
│269
11.7.17.1
Object type for output
Options:
1 bit
1 byte
■
1 bit:
– Object type for the control of RTC with 1-bit communication objects for operating mode
switchover.
■
1 byte:
– Object type for the control of RTC with 1-byte communication objects for KNX operating
mode switchover.
The parameter us used to fix the size of object "Sx: operating mode...".
For setting "1 byte" the following values are sent dependent on the setting of the "Operating
mode" parameter.
0 = auto
1 = comfort
2 = standby
3 = night
4 = frost/heat protection