Parameters 275
Defines the quick ramp set 2 acceleration time.
The time required for the speed to change from zero to the
speed value defined by parameter
. This ramp is effective in
speed/frequency range defined by parameters
and
.
10.00
0.10...20.00 s
Time
100 = 1s
Defines the quick ramp set 2 deceleration time.
The time required for the speed to change from the speed
value to zero is defined by parameters
or
. This ramp is effective in
speed/frequency range defined by parameters
and
.
10.00
0.10...20.00 s
Time
100 = 1s
Defines the maximum speed/frequency for the quick ramp 2.
Above this speed/frequency, the drive either uses quick ramp
2 or normal ramp time depending on selection in parameter
45
15...100 Hz
Frequency/Speed limit
1 = 1Hz
Selects dry run protection mode.
No action
Dry run protection is disabled.
0
Warning
warning.
1
Fault
Dry run protection generates
fault.
2
Fault if running
Dry run protection generates a fault if the source signal is
high when running.
3
Selects the source for dry run protection.
Under load curve
Activates dry run protection (parameter
, bit 0).
See section
User load curve (Condition monitoring)
(page
0
DI1
Digital input DI1.
1
DI2
Digital input DI2.
2
DI3
Digital input DI3.
3
DI4
Digital input DI4.
4
DI5
Digital input DI5.
5
DI6
Digital input DI6.
6
Supervision 1
Activates dry run protection.
7
Supervision 2
Activates dry run protection.
8
Supervision 3
Activates dry run protection.
9
Selects the drive action in case the system does not reach
the setpoint in time defined with parameter
The time is calculated with the last reference change in
parameter
No action
Soft pipe fill time-out is disabled.
0
Warning
warning.
1
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...