Parameters 191
Hysteresis
Action is taken whenever the signal rises above the value
defined by the limit + 0.5
·
hysteresis range (
). The action is deactivated when the
signal falls below the value defined by the limit - 0.5
·
hysteresis range.
7
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 6
exceeds its limits.
Note:
This parameter does not affect the status indicated by
.
No action
No warning or fault generated.
0
Warning
Warning
is generated.
1
Fault
Drive trips on fault
2
Fault if running
Drive trips on fault
if the motor is
running.
3
Selects the signal to be monitored by signal supervision
function 6.
For the available selections, see parameter
Defines a filter time constant for the signal monitored by
signal supervision 6.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 6.
0.00
-21474836.00…
21474836.00
Low limit.
-
Defines the upper limit for signal supervision 6.
0.00
-21474836.00…
21474836.00
Upper limit.
-
Defines the hysteresis for the signal monitored by signal
supervision 6.
0.00
0.00…100000.00
Hysteresis.
-
34
Configuration of the timed functions.
See also section
(page
).
Status of the combined timers. The status of a combined
timer is the logical OR of all timers connected to it.
This parameter is read-only.
-
0000h…0FFFFh
Status of combined timers 1…3.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Timed function 1
1 = Active.
1
Timed function 2
1 = Active.
2
Timed function 3
1 = Active.
3…15
Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...