Parameters 177
Enables the overvoltage control of the intermediate DC link.
Fast braking of a high inertia load causes the voltage to rise
to the overvoltage control limit. To prevent the DC voltage
from exceeding the limit, the overvoltage controller
automatically decreases the braking torque.
Note:
If the drive is equipped with a brake chopper and
resistor, or a regenerative supply unit, the controller must be
disabled.
Disable
Overvoltage control disabled.
0
Enable
Overvoltage control enabled.
1
Enables the undervoltage control of the intermediate DC link.
If the DC voltage drops due to input power cut off, the
undervoltage controller will automatically decrease the motor
torque in order to keep the voltage above the lower limit. By
decreasing the motor torque, the inertia of the load will cause
regeneration back to the drive, keeping the DC link charged
and preventing an undervoltage trip until the motor coasts to
a stop. This will act as a power-loss ride-through functionality
in systems with high inertia, such as a centrifuge or a fan.
Disable
Undervoltage control disabled.
0
Enable
Undervoltage control enabled.
1
31
Configuration of external events; selection of behavior of the
drive upon fault situations.
Defines the source of external event 1.
See also parameter
.
0 = Trigger event
1 = Normal operation
Active (false)
0.
0
Inactive (true)
1.
1
Reserved
2
DI1
Digital input DI1 (
, bit 0).
3
DI2
Digital input DI2 (
, bit 1).
4
DI3
Digital input DI3 (
, bit 2).
5
DI4
Digital input DI4 (
, bit 3).
6
DI5
Digital input DI5 (
, bit 4).
7
DI6
Digital input DI6 (
, bit 5).
8
). -
Selects the type of external event 1.
Fault
The external event generates a fault.
0
Warning
The external event generates a warning.
1
Defines the source of external event 2. See also parameter
For the selections, see parameter
Selects the type of external event 2.
Fault
The external event generates a fault.
0
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...