Fault tracing 353
4290
Cooling
Drive module temperature is
excessive.
Check ambient temperature. If it
exceeds 40 °C/104 °F (IP21 frames
R4
…
R9) or if it exceeds 50 °C /122
°F (IP21 frames R0
…
R9), ensure that
load current does not exceed derated
load capacity of drive. For all P55
frames, check the derating
temperatures. See chapter
Technical
data
, section
Derating
in the
Hardware manual
of the drive.
Check drive module cooling air flow
and fan operation.
Check inside of cabinet and heatsink
of drive module for dust pick-up.
Clean whenever necessary.
42F1
IGBT temperature
Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive
power.
4310
Excess temperature
Power unit module
temperature is excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive
power.
4380
Excess temperature
difference
High temperature difference
between the IGBTs of different
phases.
Check the motor cabling.
Check cooling of drive module(s).
4981
External temperature
1
(Editable message text)
Measured temperature 1 has
exceeded fault limit.
Check the value of parameter
.
Check the cooling of the motor (or
other equipment whose temperature
is being measured).
4982
External temperature
2
(Editable message text)
Measured temperature 2 has
exceeded fault limit.
Check the value of parameter
.
Check the cooling of the motor (or
other equipment whose temperature
is being measured).
5080
Fan
Cooling fan feedback missing.
See
5081
Auxiliary fan broken
An auxiliary cooling fan
(connected to the fan
connectors on the control unit)
is stuck or disconnected.
Check the auxiliary code.
Check auxiliary fan(s) and
connection(s).
Replace fan if faulty.
Make sure the front cover of the drive
is in place and tightened.
If the commissioning of the drive
requires th the cover is off, activate
parameter
within 2 min from control unit reboot to
temporarily suppress the fault.
Reboot the control unit (using
parameter
)
or by cycling power.
0001 Auxiliary fan 1 broken.
Code
(hex)
Fault / Aux. code
Cause
What to do
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...