338 Fault tracing
Faults latch inside the drive and cause the drive to trip, and the motor stops. After the
cause of a fault has been removed, the fault can be reset from the panel or from a
selectable source (parameter
) such as the digital inputs of
the drive. Reseting the fault creates an event
. After the reset, the
drive can be restarted.
Note that some faults require a reboot of the control unit either by switching the power
off and on, or using parameter
fault listing wherever appropriate.
Pure events
In addition to warnings and faults, there are pure events that are only recorded in the
event log of the drive. The codes of these events are included in the
table on page (
).
Editable messages
For external events, the action (fault or warning), name and the message text can be
edited. To specify external events, select
Menu
-
Primary settings
-
Advanced
functions
-
External events
.
Contact information can also be included and the text edited. To specify contact
information, select
Menu
-
Primary settings
-
Clock, region, display
-
Contact info
view
.
Warning/fault history
Event log
All indications are stored in the event log with a time stamp and other information.
The event log stores information on
• the last 8 fault recordings, that is, faults that tripped the drive or fault resets
• the last 10 warnings or pure events that occurred.
See section
Viewing warning/fault information
on page
Auxiliary codes
Some events generate an auxiliary code that often helps in pinpointing the problem.
On the control panel, the auxiliary code is stored as part of the details of the event; in
the Drive composer PC tool, the auxiliary code is shown in the event listing.
Viewing warning/fault information
The drive is able to store a list of the active faults actually causing the drive to trip at
the present time. The drive also stores a list of faults and warnings that have
previously occurred.
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...