248 Parameters
Selects the type of parity bit and number of stop bits.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
8 NONE 1
Eight data bits, no parity bit, one stop bit.
0
8 NONE 2
Eight data bits, no parity bit, two stop bits.
1
8 EVEN 1
Eight data bits, even parity bit, one stop bit.
2
8 ODD 1
Eight data bits, odd parity bit, one stop bit.
3
Takes changed EFB settings in use, or activates silent mode.
Enabled
Normal operation.
0
Refresh settings
Refreshes settings (parameters
…
) and takes changed EFB configuration
settings in use. Reverts automatically to
1
Silent mode
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
selection of this parameter.
2
Displays the status of the EFB communication.
This parameter is read-only.
Note that the name is only visible when the error is present
(bit value is 1).
-
0000h…FFFFh
EFB communication status.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Init failed
1 = EFB initialization failed
1
Addr config err
1 = Node address not allowed by protocol
2
Silent mode
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
3
Autobauding
1 = Automatic detection of baud rate is in use (see parameter
4
Wiring error
1 = Errors detected (A/B wires possibly swapped)
5
Parity error
1 = Error detected: check parameters
and
6
Baud rate error
1 = Error detected: check parameters
and
7
No bus activity
1 = 0 bytes received during last 5 seconds
8
No packets
1 = 0 packets (addressed to any device) detected during last 5
seconds
9
Noise or addressing
error
1 = Errors detected (interference, or another device with the
same address on line)
10
Comm loss
1 = 0 packets addressed to the drive received within timeout
(
11
CW/Ref loss
1 = No control word or references received within timeout (
12…14 Reserved
15
Internal error
1 = Internal error occurred. Contact your local ABB
representative.
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...