Parameters 217
FB A ref1
15
FB A ref2
16
Reserved
17…18
EFB ref1
19
EFB ref2
20
Reserved
21…23
Setpoint data
storage
(see page
).
(Selection not available for parameter
24
Compensated
setpoint
(see page
).
25
). -
Selects the second source of process setpoint. The second
source is used only if the setpoint function requires two
inputs.
For the selections, see parameter
Selects a function between the setpoint sources selected by
parameters
The result of the function (for any selection) is multiplied by
parameter
. (That is why in
selections 12 and 13, the multiplier k is constant 1.)
In1 Source
1.
0
In1+In2
Sum of sources 1 and 2.
1
In1-In2
Source 2 subtracted from source 1.
2
In1*In2
Source 1 multiplied by source 2.
3
In1/In2
Source 1 divided by source 2.
4
MIN(In1,In2)
Smaller of the two sources.
5
MAX(In1,In2)
Greater of the two sources.
6
AVE(In1,In2)
Average of the two sources.
7
sqrt(In1)
Square root of source 1.
8
sqrt(In1-In2)
Square root of (source 1 - source 2).
9
sqrt(In1+In2)
Square root of (source 1 + source 2).
10
sqrt(In1)+sqrt(In2)
Square root of source 1 + square root of source 2.
11
k*sqrt(In1)
Square root of source 1. (k = 1)
12
k*sqrt(In1-In2)
Square root of (source 1 - source 2). (k = 1)
13
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...