216 Parameters
See parameter
.
If the parameter is set to zero, scaling is automatic:
0.00
-200000.00…
200000.00
Process PID controller output base.
1 = 1
Selects the primary source of process PID setpoint. See the
control chain diagram on page
Not selected
None.
0
Reserved
1
Internal setpoint
Internal setpoint. See parameter
2
AI1 scaled
).
3
AI2 scaled
).
4
Reserved
5…7
Motor
potentiometer
(output of the motor
potentiometer).
8
Reserved
9
Freq in scaled
(see page
). 10
AI1 percent
(see page
11
AI2 percent
(see page
12
Control panel (ref
saved)
Panel reference (
, see page
saved by the control system for the location where the control
returns is used as the reference.
(Selection not available for parameter
13
Control panel (ref
copied)
Panel reference (
, see page
) for
the previous control location is used as the reference when
the control location changes if the references for the two
locations are of the same type (eg
frequency/speed/torque/PID); otherwise, the actual signal is
used as the new reference.
14
No.
Name/Value
Description
Def/FbEq16
Operation mode
(see par.
)
Scaling
Speed control
Frequency control
Ext1 -> Ext2
t
Reference
Ext1 reference
Ext2 reference
Active reference
Inactive reference
Ext1 -> Ext2
Ext1 reference
Ext2 reference
Active reference
t
Inactive reference
Reference
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...