Parameters 125
Displays the value of analog input AI1 in mA or V (depending
on whether the input is set to current or voltage by a hardware
setting).
This parameter is read-only.
-
0.000…20.000 mA
or 0.000…10.000 V
Value of analog input AI1.
1000 = 1 unit
Displays the value of analog input AI1 after scaling. See
parameters
This parameter is read-only.
-
-32768.000…
32767.000
Scaled value of analog input AI1.
1 = 1
Forced value that can be used instead of the true reading of
the input. See parameter
.
-
0.000…20.000 mA
or 0.000…10.000 V
Forced value of analog input AI1.
1000 = 1 unit
Selects the unit for readings and settings related to analog
input AI1.
V
Volts.
2
mA
Milliamperes.
10
Defines the filter time constant for analog input AI1.
Note:
The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This cannot
be changed by any parameter.
0.100 s
0.000…30.000 s
Filter time constant.
1000 = 1 s
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
.
4.000 mA or
0.000 V
0.000…20.000 mA
or 0.000…10.000 V
Minimum value of AI1.
1000 = 1 unit
No.
Name/Value
Description
Def/FbEq16
63
%
100
T
t
O = I × (1 - e
-t
/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...