Program features 45
Adaptive program fault and aux code formats
The format of the aux code:
If the state number is zero but the block number has a value, the fault is related to a
function block in the base program. If both state number and block number are zero,
the fault is a generic fault that is not related to a specific block.
Sequence program
An adaptive program can contain base program and sequence program parts. Base
program is run continuously when adaptive program is in running mode. The
functionality of the base program is programmed using function blocks and system
inputs and outputs.
Sequence program is a state machine. This means that only one state of the
sequence program is run at a time. You can create a sequence program by adding
states and programming the state programs using the same program elements as in
the base program. You can program state transitions by adding state transition
outputs to the state programs. The state transition rules are programmed using
function blocks.
The number of the active state of the sequence program is shown by parameter
Set 1 setpoint 2
Set 1 feedback 1
Set 1 feedback 2
Set 1 gain
Set 1 integration time
Set 1 tracking mode
Set 1 track reference
Bits 24-31: State number
Bits 16-23: block number
Bits 0-15: error code
Outputs available to the adaptive program
Output
Target
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...