Parameters 225
Selects the source that determines whether process PID
parameter set 1 (parameters
…
) or set 2 (group
) is used.
PID set 1
0. Process PID parameter set 1 in use.
0
PID set 2
1. Process PID parameter set 2 in use.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Reserved
8…17
Timed function 1
Bit 0 of
18
Timed function 2
Bit 1 of
19
Timed function 3
Bit 2 of
20
Supervision 1
Bit 0 of
(see page
21
Supervision 2
Bit 1 of
(see page
22
Supervision 3
Bit 2 of
(see page
23
). -
Prevention of PID integration term increase for PID set 1.
No
Increase prevention not in use.
0
Limiting
The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is valid
for the PID set 1.
1
Ext PID min lim
The process PID integration term is not increased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
2
Ext PID max lim
The process PID integration term is not increased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
3
). -
Prevention of PID integration term decrease for PID set 1.
No
Decrease prevention not in use.
0
Limiting
The PID integration term is not decreased if the minimum
value for the PID output is reached. This parameter is valid
for the PID set 1.
1
Ext PID min lim
The process PID integration term is not decreased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
2
Ext PID max lim
The process PID integration term is not decreased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
3
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...