50 Program features
The following examples describes the first, second and third stage of acceleration in
quick ramp mode.
• First stage of acceleration (a) is to lift the impeller so that the fluid protects the
bearings and sealings. Otherwise, the pump can get damaged. For example, 0 Hz
to 25/30 Hz with ramp time of 1 second.
• Second stage of acceleration (b) is an optional. The pump produces a valid flow in
this region, so the reasonable acceleration rate is requested to limit the turbidity.
The effective inside region is 25/30 to 43/45 Hz and the ramp times typically are
between 10 to 45 seconds.
• Third stage of acceleration (c) is a normal ramp. The pump provides a reasonable
flow rate. The drive uses normal ramp times, for example, 60 seconds.
Settings
•
Menu - Primary settings - Ramps
• Speed reference ramping: Parameters
(pages
and
• Frequency reference ramping: Parameters
…
(pages
and
• Motor potentiometer: Parameter
(page
• Emergency stop (“Off3” mode): Parameter
(page
• Pump protections - Quick ramps: Parameter group
(page
).
Constant speeds/frequencies
Constant speeds and frequencies are predefined references that can be quickly
activated, for example, through digital inputs. It is possible to define up to 7 speeds
for speed control and 7 constant frequencies for frequency control.
WARNING:
Speeds and frequencies override the normal reference
irrespective of where the reference is coming from.
Settings
• Parameter groups
(page
) and
(page
).
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...