146 Parameters
-DI2
Digital input DI2 (
, bit 1).
9
-DI3
Digital input DI3 (
, bit 2).
10
-DI4
Digital input DI4 (
, bit 3).
11
-DI5
Digital input DI5 (
, bit 4).
12
-DI6
Digital input DI6 (
, bit 5).
13
Fieldbus adapter
This selection cannot be used to control Start interlock with
ABB drives profile from the fieldbus adapter. Use
and map to control word user bits.
14
Embedded fieldbus
Start interlock 1: DCU profile: Inverse of control word bit 18
received through the embedded fieldbus interface.
Start interlock 2: Inverse of bit 19.
15
Source selection (see
). -
Selects the source of the Start interlock 2 signal.
For the selections, see parameter
.
Selects the source of the Start interlock 3 signal.
For the selections, see parameter
.
Selects the source of the Start interlock 4 signal.
For the selections, see parameter
.
Selects the method of stopping if a Start interlock signal is
lost. Applies to
,
and
Not used
Not in use.
0
Coast
The motor coasts to a stop.
1
Ramp
Stop along the active deceleration ramp.
2
Alternative alarm texts for the run permissive.
Run permissive
0
Valve opening
2
Pre-lube cycle
3
Alternative alarm texts for the start interlock 1.
Start interlock 1
0
Vibration switch
1
Firestat
2
Freeze stat
3
Overpressure
4
Vibration trip
5
Smoke alarm
6
Auxiliary open
7
Low suction
8
Low pressure
9
Access door
10
Pressure relief
11
Motor disconnect
open
12
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...