Parameters 237
Defines the 16-bit scaling of current parameters. The value of
this parameter corresponds to 10000 in fieldbus
communication.
10000 A
0…30000 A
Defines a speed corresponding to a zero reference received
from fieldbus (either the embedded fieldbus interface, or
interface FBA A). For example, with a setting of 500, the
fieldbus reference range of 0…20000 would correspond to a
speed of 500…[
] rpm.
Note:
This parameter is effective only with the ABB Drives
communication profile.
0.00 rpm
0.00 … 30000.00
rpm
Speed corresponding to minimum fieldbus reference.
1 = 1 rpm
Defines a filter time for signals
.
500 ms
2…20000 ms
Motor speed signal filter time.
1 = 1 ms
Defines a filter time for signal
500 ms
2…20000 ms
Output frequency signal filter time.
1 = 1 ms
Defines a filter time for signal
100 ms
2…20000 ms
Motor torque signal filter time.
1 = 1 ms
Defines a filter time for signal
.
100 ms
2…20000 ms
Output power signal filter time.
1 = 1 ms
Defines the “at setpoint” limits for speed control of the drive.
When the difference between reference (
)
is smaller than
, the drive is
considered to be “at setpoint”. This is indicated by bit 8 of
50.00 rpm
0.00…30000.00
rpm
Limit for “at setpoint” indication in speed control.
See par.
No.
Name/Value
Description
Def/FbEq16
(rpm)
0 rpm
(rpm)
(rpm)
(rpm)
Drive at setpoint
(
bit 8 = 1)
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...