Program features 55
1. The pump system meets the triggering conditions defined by parameter
. At this conditions, normal operation stops and the drive
uses the target time defined in parameter
to reach zero
speed.
2. Acceleration for cleaning is defined by parameter
.
3. The pump runs at cleaning speed for the time defined by parameter
4. The pump decelerates to zero-speed. Target time is defined by parameter
5. The pump is stopped until parameter
is elapsed.
6. The pump accelerates the pump speed to positive direction. See parameter
7. The pump runs at the positive cleaning speed. See parameter
8. The pump decreases the pump speed back to zero defined by parameter
9. The drive waits until the parameter
cleaning sequence starts or normal operation starts.
10. The pump starts following speed/frequency reference of the active control
location. During acceleration to speed/frequency, the drive follows pump cleaning
acceleration time
The drive automatically determines the fastest ramp during the pump cleaning and
used to protect the pump. It is possible that the quick ramps are faster than the pump
cleaning ramps.
The cleaning sequence starts based on the selected triggering conditions. The
cleaning sequence follows the diagram on page
. You can start the sequence in
these conditions:
• on every start and stop
• based on the monitoring pump condition (for example, supervision 1…3;
underload and overload curve, see group
on
)
• based on time interval (for example, at every 10 hours)
• manually (for example, DI4 to DI6, defined by parameter
• through fieldbus, using parameter
. Set the
parameter to a value of 1 (a 2 s pulse) from the fieldbus to start a cleaning cycle
from an overriding controller.
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...