278 Parameters
Triggered
Cleaning sequence is triggered by parameter
specifies
warning generation only.
4
Displays the pump cleaning progress.
0.0
0.0...100.0%
Percentage
10 = 1%
Displays the total cleaning count.
0
0...1000000
Total cleaning count.
1 = 1
Enables the pump cleaning action.
Off
Pump cleaning is disabled.
0
Cleaning
Pump cleaning is started based on triggers.
1
Warning only
Generates warning message based on triggers.
2
Enables/disables the pump cleaning sequence for the drive,
and defines the triggering conditions.
Note:
If DI1 remains On after cleaning is finished, no cleaning
sequence is started. The drive starts cleaning on next start, if
the trigger signal is On when motor is started.
0b0000
Starts pump cleaning.
Not active
Pump cleaning is not active.
0
Start cleaning now
Starts pump cleaning immediately.
1
DI4
Starts pump cleaning when DI4 goes high.
2
DI5
Starts pump cleaning when DI5 goes high.
3
DI4
Starts pump cleaning when DI6 goes high.
4
Source selection (see
). -
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Reserved
1
Every start
Cleaning starts at every start.
2
Every stop
Cleaning starts at every stop.
3
Reserved
4
Overload detection
Cleaning sequence starts when overload situation is
detected. To set up the overload curve, see parameters in
group
.
5
Underload detection
Cleaning sequence starts when underload situation is
detected. To set up the overload curve, see parameters in
group
.
6
Fixed time interval
Time interval defined by parameter
.
7
Combined timer1
Combined timer 1 of timed functions starts cleaning.
8...9
Reserved
10
Supervision 1
Cleaning sequence starts when Supervision 1 is high.
11
Supervision 2
Cleaning sequence starts when Supervision 2 is high.
12
Supervision 3
Cleaning sequence starts when Supervision 3 is high.
13
DI4
Cleaning sequence starts when DI4 is high.
14
DI5
Cleaning sequence starts when DI5 is high.
15
DI6
Cleaning sequence starts when DI6 is high.
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...