Parameters 277
Outlet maximum
pressure warning
level
Defines the level at which drive should generate the outlet
maximum pressure warning.
0.00
0.00...32767.00 bar Outlet maximum pressure warning level.
1 = 1 bar
Outlet maximum
pressure fault level
Defines the level at which drive should generate the outlet
maximum pressure fault.
0.00
0.00...32767.00 bar Outlet maximum pressure fault level.
1 = 1 bar
Inlet minimum
pressure protection
Enables inlet minimum pressure protection function.
Disabled
Inlet minimum pressure protection is disabled.
0
Warning
Inlet minimum pressure protection function generates
warning when the pressure is below
the level defined with parameter
for a time set in
.
1
Fault
Inlet minimum pressure protection function generates
fault when the pressure is below the
for a time set in
.
2
Warning/Fault
Inlet minimum pressure protection function first generates a
warning when the pressure is below the level defined with
parameter
Inlet minimum pressure warning level
for a
time set in
.
If the pressure continues to fall below the level defined with
parameter
Inlet minimum pressure fault level
, a fault is
generated.
3
Inlet minimum
pressure warning
level
Defines the level at which drive should generate the inlet
minimum pressure warning.
0.00
0.00...32767.00 bar Inlet minimum pressure warning level.
1 = 1 bar
Inlet minimum
pressure fault level
Defines the level at which drive should generate the inlet
minimum pressure fault.
0.00
0.00...32767.00 bar Inlet minimum pressure fault level.
1 = 1 bar
Defines the delay time at which the pressure supervisions are
inactive.
You can adjust check delay for a system in which the
pressure does not increase immediately after starting the
motor.
3.00
0.00...3600.00 s
Pressure check delay time.
1 = 1 s
83
Settings for the pump cleaning sequence.
See section
(page
Displays the status of pump cleaning.
Disabled
Cleaning sequence is disabled.
0
Pump clean
Cleaning sequence is active.
1
No triggers
configured
Triggers are not configured.
2
Waiting for
triggering
Waiting for triggering signal.
3
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...