142 Parameters
Selects the source for Hand/Off disable.
1 = Hand and/or Off buttons are disabled on the panel and in
Drive composer PC tool. Parameter
specifies which buttons are disabled or
enabled.
If the HAND/OFF disable is activated while the drive is in the
Hand mode, the mode will be automatically switched to Off
and the motor stops, and the user must start the motor again.
Not active
0 = Hand and/or Off buttons are enabled and operational.
0
Active
1 = Hand and/or Off buttons are disabled and not operational. 1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Comms
DCU profile control word bit 14 received through the
embedded fieldbus interface.
8
Selects which buttons are disabled on the panel and in the
Drive composer PC tool when parameter
is disabled.
HAND
Hand button disabled.
0
OFF and HAND
Both Off and Hand buttons disabled.
1
20
Start/stop/direction and run/start enable signal source
selection; positive/negative reference enable signal source
selection.
For information on control locations, see section
(page
Selects the source of start, stop and direction commands for
external control location 1 (EXT1).
See also parameters
…
.
Not selected
No start or stop command sources selected.
0
In1 Start
The source of the start and stop commands is selected by
parameter
. The state transitions of the
source bits are interpreted as follows:
1
Reserved
2…3
No.
Name/Value
Description
Def/FbEq16
State of source 1
(
Command
0 -> 1 (
=
)
1 (
Start
0
Stop
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...