346 Fault tracing
A8A2
RO toggle warning
The relay output is changing
states faster than
recommended, eg. if a fast
changing frequency signal is
connected to it. The relay
lifetime will be exceeded
shortly.
Replace the signal connected to the
relay output source with a less
frequently changing signal.
0001 Relay output 1
Select a different signal with parameter
0002 Relay output 2
Select a different signal with parameter
0003 Relay output 3
Select a different signal with parameter
A8B0
ABB Signal
supervision 1
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision function 1.
Check the source of the warning
(parameter
A8B1
ABB Signal
supervision 2
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision function 2.
Check the source of the warning
(parameter
A8B2
ABB Signal
supervision 3
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision function 3.
Check the source of the warning
(parameter
A8B3
ABB Signal
supervision 4
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision function 4.
Check the source of the warning
(parameter
A8B4
ABB Signal
supervision 5
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision function 5.
Check the source of the warning
(parameter
A8B5
ABB Signal
supervision 6
(Editable message text)
Programmable warning:
Warning generated by the
signal supervision function 6.
Check the source of the warning
(parameter
A8BE
ULC overload
warning
Programmable fault:
Selected signal has exceeded
the user overload curve.
Check for any operating conditions
increasing the monitored signal (for
example, the loading of the motor if the
torque or current is being monitored).
Check the definition of the load curve
(parameter group
Code
(hex)
Warning / Aux. code Cause
What to do
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...