Parameters 199
On
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
). -
Defines the time inside which the extra time is deactivated
after extra time activation signal is switched off.
Example:
set to
is set to 00 01:30,
the extra time is active for 1 hour and 30 minutes after digital
input DI is deactivated.
00 00:00
00 00:00…07 00:00 Extra time duration.
1 = 1
35
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and motor
fan control configuration.
See also section
Displays the motor temperature as estimated by the internal
motor thermal protection model (see parameters
). The unit is selected by parameter
This parameter is read-only.
-
-60…1000 °C or
-76…1832 °F
Estimated motor temperature.
1 = 1°
Displays the temperature received through the source
defined by parameter
. The unit is
selected by parameter
.
Note:
With a PTC sensor, the value shown is not a valid
measurement. Either 0 ohm (normal temperature) or the
value of parameter
(excessive
temperature) is shown.
This parameter is read-only.
-
-60…5000 °C or
-76…9032 °F,
0 ohm or
[
] ohm
Measured temperature 1.
1 = 1 unit
Displays the temperature received through the source
defined by parameter
. The unit
.
Note:
With a PTC sensor, the value shown is not a valid
measurement. Either 0 ohm (normal temperature) or the
value of parameter
(excessive
temperature) is shown.
This parameter is read-only.
-
-60…5000 °C or
-76…9032 °F,
0 ohm or
[
] ohm
Measured temperature 2.
1 = 1 unit
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...