206 Parameters
Defines the thermal time constant for use with the motor
thermal protection model, defined as the time to reach 63% of
the nominal motor temperature. See the motor
manufacturer's recommendations.
For thermal protection according to UL requirements for
NEMA class motors, use the rule of thumb: Motor thermal
time equals 35 times t6, where t6 (in seconds) is specified by
the motor manufacturer as the time that the motor can safely
operate at six time its rated current.
The thermal time for Class 10 trip curve is 350 s, for Class 20
trip curve 700 s and for Class 30 trip curve 1050 s.
256 s
100…10000 s
Motor thermal time constant.
1 = 1 s
36
Peak value and amplitude logger settings.
See also section
(page
Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter
The peak value is stored, along with other pre-selected
signals at the time, into parameters
.
The peak value logger can be reset using parameter
. The logger is also reset whenever the signal
source is changed. The date and time of the last reset are
stored into parameters
and
respectively.
Not selected
None (peak value logger disabled).
0
Motor speed used
(page
1
Reserved
2
Output frequency
(page
).
3
Motor current
(page
4
Reserved
5
Motor torque
(page
).
6
No.
Name/Value
Description
Def/FbEq16
100%
63%
100%
Time
Time
Motor thermal time
Motor current
Temperature rise
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...