258 Parameters
0...8
IPC node number.
Selects if this pump operate as a master drive of the IPC
system. The master drive must have sensor connection in
order to control the process.
Not selected
The drive can only be a follower on a inverter-to-inverter link.
Selected
The drive can be a master on a inverter-to-inverter link.
Total number of motors used in the application, including the
motor connected directly to the drive.
Note:
Parameters are dynamically hidden based on selection
of number of motors.
1
1…8
Number of motors.
1 = 1
Minimum number of motors running simultaneously.
1
0…8
Minimum number of motors.
1 = 1
Maximum number of motors running simultaneously.
1
1…8
Maximum number of motors.
1 = 1
No.
Name/Value
Description
Def/FbEq16