Fieldbus control through the embedded fieldbus interface (EFB) 385
Exception codes
The table below shows the Modbus exception codes supported by the embedded
fieldbus interface.
2Bh / 0Eh
Encapsulated Interface
Transport
Supported subcodes:
• 0Eh Read Device Identification: Allows reading the
identification and other information.
Supported ID codes (access type):
• 00h: Request to get the basic device identification
(stream access)
• 04h: Request to get one specific identification
object (individual access)
Supported Object IDs:
• 00h: Vendor Name (“ABB”)
• 01h: Product Code (for example, “AQAKx”)
• 02h: Major Minor Revision (combination of contents
of parameters
• 03h: Vendor URL (“www.abb.com”)
• 04h: Product name: (“ACQ580”).
Code
Name
Description
01h
ILLEGAL FUNCTION
The function code received in the query is not an
allowable action for the server.
02h
ILLEGAL ADDRESS
The data address received in the query is not an
allowable address for the server.
03h
ILLEGAL VALUE
The requested quantity of registers is larger than the
device can handle. This error does not mean that a
value written to the device is outside of the valid
range.
04h
DEVICE FAILURE
An unrecoverable error occurred while the server was
attempting to perform the requested action. See
section
Error code registers (holding registers
.
Code
Function name
Description
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...