Parameters 115
ACQ580 specific status word.
This parameter is read-only.
-
0000h…FFFFh
Start inhibit status word.
1 = 1
Selects a binary source whose status is transmitted as bit 11
(User bit 0) of
.
False
0.
0
True
1.
1
Ext ctrl loc
Bit 11 of
(see page
).
2
). -
Selects a binary source whose status is transmitted as bit 12
(User bit 1) of
.
False
0.
0
True
1.
1
Run permissive
Status of the external run permissive signal (see parameter
).
3
). -
Selects a binary source whose status is transmitted as bit 13
(User bit 2) of
.
False
0.
0
True
1.
1
). -
Selects a binary source whose status is transmitted as bit 14
(User bit 3) of
.
False
0.
0
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Hand mode
0 = Drive is not operated from the panel in the Hand mode; 1 =
Drive is operated from the panel in the Hand mode
1
Off mode
0 = Drive is not in the Off mode; 1 = Drive is in the Off mode.
2
Auto mode
0 = Drive is not in the Auto mode; 1 = Drive is in the Auto mode.
3
Reserved
4
Pre-heating
0 = Motor pre-heating is not active; 1 = Motor pre-heating is
active.
5
Damper control
0 = Damper control is not active; 1 = Damper control is active.
6
Reserved
7
Run permissive
0 = Run permissive is not present, drive is not allowed to run; 1 =
Run permissive is present, drive is allowed to run.
8
Start interlock 1
0 = Start interlock 1 is not present, drive is not allowed to start;
1 = Start interlock 1 is present, drive is allowed to start.
9
Start interlock 2
0 = Start interlock 2 is not present, drive is not allowed to start;
1 = Start interlock 2 is present, drive is allowed to start.
10
Start interlock 3
0 = Start interlock 3 is not present, drive is not allowed to start;
1 = Start interlock 3 is present, drive is allowed to start.
11
Start interlock 4
0 = Start interlock 4 is not present, drive is not allowed to start;
1 = Start interlock 4 is present, drive is allowed to start.
12…15 Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...