170 Parameters
When bit 0 of parameter
is
0 (Separate), selects a source that activates constant
frequency 1.
When bit 0 of parameter
is
1 (Packed), this parameter and parameters
and
select
three sources whose states activate constant frequencies as
follows:
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Reserved
8…17
Timed function 1
18
Timed function 2
19
Timed function 3
20
Reserved
21…23
Supervision 1
24
Supervision 2
25
Supervision 3
26
Source selection (see
). -
When bit 0 of parameter
is
0 (Separate), selects a source that activates constant
frequency 2.
When bit 0 of parameter
is
1 (Packed), this parameter and parameters
and
select
three sources that are used to activate constant frequencies.
See table at parameter
.
For the selections, see parameter
No.
Name/Value
Description
Def/FbEq16
Source defined
Source defined
Source defined
Constant frequency
active
0
0
0
None
1
0
0
Constant frequency 1
0
1
0
Constant frequency 2
1
1
0
Constant frequency 3
0
0
1
Constant frequency 4
1
0
1
Constant frequency 5
0
1
1
Constant frequency 6
1
1
1
Constant frequency 7
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...