308 Additional parameter data
13.29 AO2 out at AO2 src min
0.000…22.000
mA
1000 = 1 mA
13.30 AO2 out at AO2 src max
0.000…22.000
mA
1000 = 1 mA
13.91 AO1 data storage
-327.68…327.67
-
100 = 1
13.92 AO2 data storage
-327.68…327.67
-
100 = 1
15 I/O extension module
15.01 Extension module type
0…3
-
1 = 1
15.02 Detected extension module
0…3
-
1 = 1
15.03 DI status
0000h…FFFFh
-
1 = 1
15.04 RO/DO status
0000h…FFFFh
-
1 = 1
15.05 RO/DO force selection
0000h…FFFFh
-
1 = 1
15.06 RO/DO forced data
0000h…FFFFh
-
1 = 1
15.07 RO4 source
-
-
1 = 1
15.08 RO4 ON delay
0.0…3000.0
s
10 = 1 s
15.09 RO4 OFF delay
0.0…3000.0
s
10 = 1 s
15.10 RO5 source
-
-
1 = 1
15.11 RO5 ON delay
0.0…3000.0
s
10 = 1 s
15.12 RO5 OFF delay
0.0…3000.0
s
10 = 1 s
15.22 DO1 configuration
0, 2
-
1 = 1
15.23 DO1 source
-
-
1 = 1
15.24 DO1 ON delay
0.0…3000.0
s
10 = 1 s
15.25 DO1 OFF delay
0.0…3000.0
s
10 = 1 s
15.32 Freq out 1 actual value
0…16000
Hz
1 = 1 Hz
15.33 Freq out 1 source
-
-
1 = 1
15.34 Freq out 1 src min
-32768.0…32767.0
-
1000 = 1
15.35 Freq out 1 src max
-32768.0…32767.0
-
1000 = 1
15.36 Freq out 1 at src min
0…16000
Hz
1 = 1 Hz
15.37 Freq out 1 at src max
0…16000
Hz
1 = 1 Hz
19 Operation mode
19.01 Actual operation mode
1…2, 10, 20
-
1 = 1
19.11 Ext1/Ext2 selection
-
-
1 = 1
19.18 HAND/OFF disable source
-
-
1 = 1
19.19 HAND/OFF disable action
0…1
-
1 = 1
20 Start/stop/direction
20.01 Ext1 commands
0…1, 4, 11…12, 14
-
1 = 1
20.02 Ext1 start trigger type
0…1
-
1 = 1
20.03 Ext1 in1 source
-
-
1 = 1
No.
Name
Type
Range
Unit
FbEq32
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...