358 Fault tracing
80A0
AI supervision
Programmable fault:
An analog signal is outside the
limits specified for the analog
input.
Check signal level at the analog input.
Check the auxiliary code.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
.
0001 AI1LessMIN
0002 AI1GreaterMAX
0003 AI2LessMIN.
0004 AI2GreaterMAX
80B0
Signal supervision 1
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision function 1.
Check the source of the fault
(parameter
).
80B1
Signal supervision 2
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision function 2.
Check the source of the fault
(parameter
).
80B2
Signal supervision 3
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision function 3.
Check the source of the fault
(parameter
).
80B3
Signal supervision 4
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision function 4.
Check the source of the fault
(parameter
).
80B4
Signal supervision 5
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision function 5.
Check the source of the fault
(parameter
).
80B5
Signal supervision 6
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision function 6.
Check the source of the fault
(parameter
).
9081
External fault 1
(Editable message text)
Programmable fault:
Fault in external device 1.
Check the external device.
Check setting of parameter
9082
External fault 2
(Editable message text)
Programmable fault:
Fault in external device 2.
Check the external device.
Check setting of parameter
9083
External fault 3
(Editable message text)
Programmable fault:
Fault in external device 3.
Check the external device.
Check setting of parameter
Code
(hex)
Fault / Aux. code
Cause
What to do
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...