90
YORK INTERNATIONAL
SW. 2 on the Microprocessor Board must also be pro-
grammed for “LOW AMBIENT CONTROL” to allow op-
eration at temperatures below 25°F. To accomplish this,
place SW. 2 in the CLOSED position. See page 37. Af-
ter the switch is properly positioned, the OUTSIDE AIR
TMP LOW CUTOUT in the PROGRAM mode can then
be programmed between 0° - 25°F (-17.8 to -3.9°C). See
page 44.
NOTE: For operation below 0°F (-17.8°C), program the
cutout for 0°F (-17.8°C). This will cause the mi-
croprocessor to ignore the low ambient cutout
regardless of temperature.
Operation of the fans will be discussed in both “Ambient
and Pressure Control” as well as “Pressure Only” con-
trol in the following text.
Ambient and Pressure Fan Control
0°F - 25°F (-17.8 to -3.9°C)
Fan operation on each system below 25°F (-3.9°C) is
controlled only by the discharge pressure of the respec-
tive system. Each system will operate 4 steps of fan
control as follows:
1.
Until discharge pressure reaches 320 PSIG (2.2
mPa), the fans will be completely off.
2.
The second stage of fan control will energize fans 1
& 3 (SYS 1, 9M & 10M) or fans 5 & 7 (SYS 2, 15M
& 16M) in the reverse direction when the discharge
pressure exceeds 320 PSIG (2.2 mPa). Once the
reversing contactors are energized, they will stay on
until the discharge pressure of the system falls be-
low 120 PSIG (827.4 kPa), the ambient temperature
exceeds 35°F (1.7°C), or discharge pressure of the
system rises above 340 PSIG (2.3 mPa).
NOTE: The corresponding compressor must be on for
a minimum of 4 seconds before the reversing
fans are permitted to start.
3.
The third stage of fan control will energize fans 2 & 4
(SYS 1, 6M & 8M) or fans 6 & 8 (SYS 2, 12M &
14M) as well as turn off the reversing fans on the
respective system whenever discharge pressure
exceeds 340 PSIG (2.3 mPa). These fans will stay
on until discharge pressure drops below 120 PSIG
(827.4 kPa).
NOTE: The corresponding compressor must be on for
4 sec. before these fans are permitted to start.
4.
The fourth stage of fan control will energize fans 1 &
3 (SYS 1, 5M & 7M) or fans 5 & 7 (SYS 2, 11M &
13M) and will operate the corresponding fans in the
forward direction whenever discharge pressure ex-
ceeds 360 PSIG (2.5 mPa). These fans will stay on
until discharge pressure drops below 140 PSIG
(965.3 kPa).
NOTE: The corresponding compressor must be on for
4 seconds before these fans are permitted to
start.
Ambient and Pressure Fan Control
25° - 45°F (-3.9 to 7.2°C)
Fan control between 25° and 35°F (-3.9 and 1.7°C) is
controlled by discharge pressure. If the reversing fans
are on, the reversing fan will continue to operate until the
temperature reaches 35°F (1.7°C) or discharge pressure
reaches 340 PSIG (2.3 mPa). At 35°F (1.7°C) or 340
PSIG (2.3 mPa), fans 2 & 4 (SYS 1, 6M & 8M) or fans 6
& 8 (SYS 2, 12M & 14M) will energize. Between 25°F
and 45°F (-3.9 and 7.2°C) if the reversing fan is not oper-
ating, after 4 seconds of compressor operation fans 2 &
4 (SYS 1) or 7 & 8 (SYS 2) will energize. This is identi-
cal to standard fan control by temperature (Page 78). No
pressure override exists. If temperature drops below 25°F
(-3.9°C), these tans will remain on until cycled off by
pressure.
Ambient and Pressure Fan Control
45°F (7.2°C) and Higher
Fan control above 45°F (7.2°C) is strictly controlled by
temperature with no pressure override.
After 4 seconds of operation, fans 2 & 4 (SYS 1, 6M &
8M) or fans 6 & 8 (SYS 2, 12M & 14M) will energize
turning the fan in the forward direction.
After 30 seconds of operation, fans 1 & 3 (SYS 1, 5M &
7M) or fans 5 & 7 (SYS 2, 11M & 13M) will energize
turning two additional fans on in the forward direction.
This is identical to standard fan control by temperature
(Page 78). These fans will de-energize if ambient tem-
perature drops below 40°F (4.4°C).
Pressure Control Only,
Fan Control by Discharge Pressure
Fan control by pressure will operate 4 stages of fan cy-
cling according to the discharge pressure of the corre-
sponding system. Ambient temperature will have no ef-
fect.
1.
Until discharge pressure reaches 320 PSIG (2.2
mPa), no system fans will operate.
2.
When discharge pressure reaches 320 PSIG (2.2
mPa) fans 1 & 3 (SYS 1, 9M & 10M) or fans 5 & 7
(SYS 2, 15M & 16M) will be energized in the reverse
direction. These fans will remain energized until dis-
charge pressure drops below 120 PSIG.
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...