FORM 150.65-NM4
79
YORK INTERNATIONAL
SYS. 1
SYS. 2
AMBIENT
AMBIENT
FANS
FANS
ON
OFF
2 & 4
6 & 8
25°F (-3.9°C)
24°F (-4.4°C)
1 & 3
5 & 7
45°F (7.2°C)
40°F (4.4°C)
FIG. 27 – FAN LOCATIONS
LD02668
FAN CONTROL STRATEGY
ABOVE 25°F (-3.9°C) AMBIENT
The chiller is equipped with 8 condenser fans; 4 per sys-
tem. The standard fan control strategy is fan cycling by
outdoor ambient temperature, with the low ambient cut-
out (chiller shut down) set at 25°F (-3.9°C).
Above 25°F (-3.9°C) ambient, 2 fans on a respective sys-
tem will turn on 4 seconds after the compressor starts.
These fans will continue to run until the compressor shuts
down. These fans are designated as Fans 2 & 4 on SYS
1 and Fans 6 & 8 on SYS 2.
If the ambient temperature is above 45°F (7.2°C), 2 or
more fans on a respective system will start after the com-
pressor has run for 30 seconds. These two fans will con-
tinue to run until the compressor shuts down or until the
ambient temperature drops to 40°F (4.4°C). These fans
are designated as Fans 1 & 3 on SYS 1 and Fans 5 & 7
on SYS 2.
Locations of the fans and a chart showing the operation
outlined above is shown in Fig. 27.
For operation below 25°F (-3.9°C), a Low Ambient Kit
MUST be installed. See page 89.
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...