32
YORK INTERNATIONAL
25998A
FIG. 10 – POWER PANEL
POWER SUPPLY BOARD
The on-board switching power supply converts 24VAC
from the 2T transformer to +12V REG which is supplied
to the Microprocessor Board, Relay Board, and 40 Char-
acter Display to operate integrated circuitry.
A rectifier and filtering circuit for each motor current cir-
cuit rectifies and filters these signals to variable DC.
These signals are then fed to the Microprocessor Board.
RELAY OUTPUT BOARD
This board converts 0 - 12VDC logic level outputs from
the Microprocessor Board to 120VAC levels used by
motor contactors, solenoid valves, etc. to control sys-
tem operation. The common side of all relays on the
Relay Output Board is converted to +12V REG.
The open collector outputs of the Microprocessor Board
energize the DC relays by pulling the other side of the
relay coil to ground. When not energized, both sides of
the relay coils will be at +12VDC potential.
I/O EXPANSION BOARD
The I/O Expansion Board allows the MicroComputer to
receive additional analog inputs from Oil Temperature Sen-
sors and optional Discharge Temperature Sensors.
These inputs are multiplexed and sent to the Micropro-
cessor Board to allow the MicroComputer to monitor
these inputs for display and as safeties.
CURRENT TRANSFORMER (C.T.)
A C.T. on the 3
φ
power wiring of each motor sends AC
signals proportional to motor current to the Power Sup-
ply Board which rectifies and filters the signal to variable
DC voltage (analog). This analog level is then fed to the
Microprocessor Board to allow it to monitor motor cur-
rent.
40 CHARACTER DISPLAY
The 40 Character Display (2 lines of 20 characters) is a
liquid crystal display used for displaying system param-
eters and operator messages. The display has a lighted
background for night viewing as well as a special feature
which intensifies the display for viewing in direct sun-
light.
KEYPAD
An operator keypad allows complete control of the sys-
tem from a central location. The keypad offers a multi-
tude of commands available to access displays, pro-
gram setpoints, and initiate system commands.
BATTERY BACK-UP
The Microprocessor Board contains a Real Time Clock
integrated circuit chip with an internal battery back-up.
The purpose of this battery back-up is to assure any
programmed values (setpoints, clock, cut-outs, etc.) are
not lost during a power failure regardless of the time in-
volved in a power outage or shutdown period.
1 & 2 FUSE
SYS 2 FAN
CONTACTORS
SYS 2 FAN
OVERLOADS
SYS 2
POWER WIRING
CONNECTION
POINT
TB1 CONNECTIONS
FOR OPTIONAL
ALARMS, EVAP.
PUMP, COND.
PUMP AND L & 2
115VAC CONTROL
PANEL SUPPLY
SYS 1 FAN
CONTACTORS
SYS 1 FAN
OVERLOADS
SYS 1
POWER WIRING
CONNECTION
POINT
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...